A load takes 31 kW of real power and 10 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A single-phase load connected to a 120 V supply takes 14 kW and 9 kvar. Find the current I drawn from the supply.
A single-phase motor takes 10 kW at a power factor of 0.65 lagging from a 400 V supply. Find the line current I.
A single-phase motor takes 37 kW at a power factor of 0.8 lagging from a 400 V supply. Find the reactive power Q it draws.
A 10 V (rms), 1000 Hz source has an internal impedance Zs = 20 + j40 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 50 kW at a power factor of 0.6 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the capacitance C needed.
Answer key
- 1. cos φ = 0.9517
- 2. I = 138.7 A
- 3. I = 38.46 A
- 4. Q = 27.75 kvar
- 5. Pmax = 1.25 W
- 6. C = 2730 µF
Full step-by-step solutions: practise this topic on examproblems.com.