A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 19.5 A and 4212 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 18.5 A and 2109 W. Find the power factor cos φ of the load.
An inductive load takes 6 A and 828 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
An inductive load takes 3.5 A and 357 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase load takes 5 kW at a power factor of 0.65 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the capacitance C needed.
A 150 kVA single-phase transformer supplies a load of 78 kW at a power factor of 0.7 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. cos φ = 0.9
- 2. cos φ = 0.95
- 3. X = 30.67 Ω
- 4. X = 18.06 Ω
- 5. C = 171.7 µF
- 6. ΔP = 49.15 kW
Full step-by-step solutions: practise this topic on examproblems.com.