A single-phase load draws 17 A (rms) from a 400 V (rms) supply at a power factor of 0.75 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load draws 13 A (rms) from a 400 V (rms) supply at a power factor of 0.9 lagging. Find the reactive power Q it takes.
A single-phase motor takes 36 kW at a power factor of 0.7 lagging from a 230 V supply. Find the reactive power Q it draws.
A load with impedance Z = 16 + j12 Ω is connected to a 120 V (rms) single-phase supply. Find the apparent power S.
A single-phase load takes 40 kW at a power factor of 0.8 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the new line current Inew.
A single-phase load takes 45 kW at a power factor of 0.7 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
Answer key
- 1. P = 5100 W
- 2. Q = 2267 var
- 3. Q = 36.73 kvar
- 4. S = 720 VA
- 5. Inew = 102 A
- 6. Inew = 208.3 A
Full step-by-step solutions: practise this topic on examproblems.com.