A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 8 A and 1656 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 17.5 A and 2520 W. Find the power factor cos φ of the load.
An inductive load takes 13.5 A and 2484 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A load with impedance Z = 9 + j12 Ω is connected to a 240 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase load takes 40 kW at a power factor of 0.7 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the reactive power QC the capacitor must supply.
A 200 kVA single-phase transformer supplies a load of 61 kW at a power factor of 0.65 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. cos φ = 0.9
- 2. cos φ = 0.6
- 3. R = 13.63 Ω
- 4. Q = 3072 var
- 5. QC = 23.77 kvar
- 6. ΔP = 125.9 kW
Full step-by-step solutions: practise this topic on examproblems.com.