A load takes 39.5 kW of real power and 41.5 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A single-phase load draws 10 A (rms) from a 240 V (rms) supply at a power factor of 0.7 lagging. Find the reactive power Q it takes.
A single-phase motor takes 13 kW at a power factor of 0.9 lagging from a 230 V supply. Find the line current I.
A single-phase motor takes 35 kW at a power factor of 0.9 lagging from a 400 V supply. Find the reactive power Q it draws.
A single-phase load takes 35 kW at a power factor of 0.7 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.
A single-phase load takes 35 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the capacitance C needed.
Answer key
- 1. S = 57.29 kVA
- 2. Q = 1714 var
- 3. I = 62.8 A
- 4. Q = 16.95 kvar
- 5. Inew = 158.5 A
- 6. C = 517.4 µF