A load takes 41.5 kW of real power and 32 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A single-phase load draws 13 A (rms) from a 230 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
Two loads are connected in parallel to a 240 V single-phase supply: a 29 kW load at a power factor of 0.7 lagging and a 5 kW load at a power factor of 0.9 leading. Find the overall power factor cos φ seen by the supply.
A single-phase motor takes 27 kW at a power factor of 0.75 lagging from a 400 V supply. Find the line current I.
A 100 V (rms), 50 Hz source has an internal impedance Zs = 2 + j20 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A 200 kVA single-phase transformer supplies a load of 109 kW at a power factor of 0.65 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. cos φ = 0.7919
- 2. Q = 2272 var
- 3. cos φ = 0.7813
- 4. I = 90 A
- 5. Pmax = 1250 W
- 6. ΔP = 45.14 kW