A single-phase load draws 11 A (rms) from a 240 V (rms) supply at a power factor of 0.7 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load draws 8 A (rms) from a 230 V (rms) supply at a power factor of 0.7 lagging. Find the real power P it takes.
A load with impedance Z = 20 + j15 Ω is connected to a 120 V (rms) single-phase supply. Find the apparent power S.
Two loads are connected in parallel to a 230 V single-phase supply: a 15 kW load at a power factor of 0.6 lagging and a 25 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
A single-phase load takes 35 kW at a power factor of 0.6 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the reactive power QC the capacitor must supply.
A single-phase load takes 13 kW at a power factor of 0.6 lagging from a 230 V, 60 Hz supply. A 330 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. Q = 1885 var
- 2. P = 1288 W
- 3. S = 576 VA
- 4. cos φ = 0.8944
- 5. QC = 29.72 kvar
- 6. I = 73.35 A