A single-phase load draws 2 A (rms) from a 240 V (rms) supply at a power factor of 0.6 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 18 A and 1728 W. Find the power factor cos φ of the load.
A single-phase motor takes 34 kW at a power factor of 0.65 lagging from a 400 V supply. Find the line current I.
A single-phase motor takes 18 kW at a power factor of 0.65 lagging from a 240 V supply. Find the reactive power Q it draws.
A single-phase load takes 20 kW at a power factor of 0.75 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the capacitance C needed.
A single-phase load takes 25 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the new line current Inew.
Answer key
- 1. Q = 384 var
- 2. cos φ = 0.8
- 3. I = 130.8 A
- 4. Q = 21.04 kvar
- 5. C = 478.5 µF
- 6. Inew = 65.79 A