A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 11 A and 2024 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load draws 12 A (rms) from a 120 V (rms) supply at a power factor of 0.65 lagging. Find the real power P it takes.
A load with impedance Z = 5 + j12 Ω is connected to a 230 V (rms) single-phase supply. Find the apparent power S.
Two loads are connected in parallel to a 400 V single-phase supply: a 2 kW load at a power factor of 0.75 lagging and a 6 kW load at a power factor of 0.95 lagging. Find the overall power factor cos φ seen by the supply.
A single-phase load takes 5 kW at a power factor of 0.7 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the new line current Inew.
A single-phase load takes 20 kW at a power factor of 0.7 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the reactive power QC the capacitor must supply.
Answer key
- 1. cos φ = 0.8
- 2. P = 936 W
- 3. S = 4069 VA
- 4. cos φ = 0.9061
- 5. Inew = 21.93 A
- 6. QC = 16.34 kvar