A single-phase load draws 3 A (rms) from a 230 V (rms) supply at a power factor of 0.9 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load connected to a 230 V supply takes 23.5 kW and 14.5 kvar. Find the current I drawn from the supply.
Two loads are connected in parallel to a 230 V single-phase supply: a 22 kW load at a power factor of 0.65 lagging and a 6 kW heater (unity power factor). Find the total current I drawn from the supply.
Two loads are connected in parallel to a 400 V single-phase supply: a 29 kW load at a power factor of 0.8 lagging and a 7 kW load at a power factor of 0.9 lagging. Find the total current I drawn from the supply.
A 150 kVA single-phase transformer supplies a load of 42 kW at a power factor of 0.85 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 20 kW at a power factor of 0.65 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the capacitance C needed.
Answer key
- 1. Q = 300.8 var
- 2. I = 120.1 A
- 3. I = 165.3 A
- 4. I = 109.8 A
- 5. ΔP = 105.7 kW
- 6. C = 684.5 µF