A single-phase load draws 8 A (rms) from a 240 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A load takes 47 kW of real power and 23 kvar of reactive power (lagging). Find the apparent power S.
A single-phase motor takes 16 kW at a power factor of 0.6 lagging from a 230 V supply. Find the line current I.
An inductive load takes 3.5 A and 714 W from a 240 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A single-phase load takes 30 kW at a power factor of 0.7 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.
A 200 kVA single-phase transformer supplies a load of 81 kW at a power factor of 0.75 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. Q = 1459 var
- 2. S = 52.33 kVA
- 3. I = 115.9 A
- 4. R = 58.29 Ω
- 5. Inew = 141.8 A
- 6. ΔP = 105.8 kW