A load takes 16.5 kW of real power and 17.5 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A single-phase load draws 17 A (rms) from a 230 V (rms) supply at a power factor of 0.75 lagging. Find the reactive power Q it takes.
A single-phase motor takes 25 kW at a power factor of 0.75 lagging from a 400 V supply. Find the reactive power Q it draws.
An inductive load takes 8 A and 1104 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A 100 V (rms), 1000 Hz source has an internal impedance Zs = 5 + j20 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
A single-phase load takes 5 kW at a power factor of 0.6 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
Answer key
- 1. cos φ = 0.686
- 2. Q = 2586 var
- 3. Q = 22.05 kvar
- 4. X = 23 Ω
- 5. C = 7.958 µF
- 6. Inew = 13.89 A