A single-phase load draws 5 A (rms) from a 230 V (rms) supply at a power factor of 0.7 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A load takes 33 kW of real power and 22 kvar of reactive power (lagging). Find the apparent power S.
A single-phase motor takes 4 kW at a power factor of 0.7 lagging from a 240 V supply. Find the line current I.
An inductive load takes 9.5 A and 1857 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A 10 V (rms), 60 Hz source has an internal impedance Zs = 20 + j5 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 50 kW at a power factor of 0.8 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the new line current Inew.
Answer key
- 1. Q = 821.3 var
- 2. S = 39.66 kVA
- 3. I = 23.81 A
- 4. X = 12.76 Ω
- 5. Pmax = 1.25 W
- 6. Inew = 219.3 A
Full step-by-step solutions: practise this topic on examproblems.com.