A load takes 22.5 kW of real power and 12.5 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 2.5 A and 431 W. Find the power factor cos φ of the load.
A single-phase motor takes 33 kW at a power factor of 0.85 lagging from a 400 V supply. Find the line current I.
A single-phase motor takes 2 kW at a power factor of 0.75 lagging from a 240 V supply. Find the reactive power Q it draws.
A single-phase load takes 20 kW at a power factor of 0.8 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.
A single-phase load takes 35 kW at a power factor of 0.8 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
Answer key
- 1. cos φ = 0.8742
- 2. cos φ = 0.7496
- 3. I = 97.06 A
- 4. Q = 1.764 kvar
- 5. Inew = 94.52 A
- 6. Inew = 162 A
Full step-by-step solutions: practise this topic on examproblems.com.