A single-phase load draws 18 A (rms) from a 230 V (rms) supply at a power factor of 0.6 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A load takes 48 kW of real power and 32 kvar of reactive power (lagging). Find the power factor cos φ.
A single-phase motor takes 39 kW at a power factor of 0.8 lagging from a 240 V supply. Find the reactive power Q it draws.
Two loads are connected in parallel to a 400 V single-phase supply: a 12 kW load at a power factor of 0.75 lagging and a 29 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
A single-phase load takes 50 kW at a power factor of 0.65 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the capacitance C needed.
A single-phase load takes 30 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the capacitance C needed.
Answer key
- 1. P = 2484 W
- 2. cos φ = 0.8321
- 3. Q = 29.25 kvar
- 4. cos φ = 0.9683
- 5. C = 2529 µF
- 6. C = 764.3 µF
Full step-by-step solutions: practise this topic on examproblems.com.