A load takes 41 kW of real power and 44.5 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A single-phase load draws 18 A (rms) from a 230 V (rms) supply at a power factor of 0.7 lagging. Find the real power P it takes.
A single-phase motor takes 24 kW at a power factor of 0.85 lagging from a 400 V supply. Find the line current I.
Two loads are connected in parallel to a 230 V single-phase supply: a 15 kW load at a power factor of 0.65 lagging and a 10 kW load at a power factor of 0.85 leading. Find the total current I drawn from the supply.
A 10 kVA single-phase transformer supplies a load of 5 kW at a power factor of 0.85 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A 200 kVA single-phase transformer supplies a load of 72 kW at a power factor of 0.65 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. S = 60.51 kVA
- 2. P = 2898 W
- 3. I = 70.59 A
- 4. I = 119.4 A
- 5. ΔP = 4.508 kW
- 6. ΔP = 109.4 kW