A single-phase load draws 11 A (rms) from a 230 V (rms) supply at a power factor of 0.8 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 13 A and 2691 W. Find the power factor cos φ of the load.
Two loads are connected in parallel to a 400 V single-phase supply: a 29 kW load at a power factor of 0.6 lagging and an 8 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
An inductive load takes 8 A and 1632 W from a 240 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A single-phase load takes 50 kW at a power factor of 0.65 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the reactive power QC the capacitor must supply.
A single-phase load takes 25 kW at a power factor of 0.7 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the reactive power QC the capacitor must supply.
Answer key
- 1. Q = 1518 var
- 2. cos φ = 0.9
- 3. cos φ = 0.6914
- 4. R = 25.5 Ω
- 5. QC = 37.16 kvar
- 6. QC = 17.29 kvar