A single-phase load draws 14 A (rms) from a 230 V (rms) supply at a power factor of 0.75 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A load takes 31.5 kW of real power and 38 kvar of reactive power (lagging). Find the apparent power S.
A single-phase motor takes 29 kW at a power factor of 0.9 lagging from a 240 V supply. Find the line current I.
A single-phase motor takes 8 kW at a power factor of 0.6 lagging from a 400 V supply. Find the line current I.
A single-phase load takes 24 kW at a power factor of 0.8 lagging from a 240 V, 50 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A 150 kVA single-phase transformer supplies a load of 42 kW at a power factor of 0.8 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. P = 2415 W
- 2. S = 49.36 kVA
- 3. I = 134.3 A
- 4. I = 33.33 A
- 5. cos φ = 0.8635
- 6. ΔP = 104.7 kW
Full step-by-step solutions: practise this topic on examproblems.com.