A single-phase load draws 7 A (rms) from a 120 V (rms) supply at a power factor of 0.95 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A load takes 30.5 kW of real power and 20.5 kvar of reactive power (lagging). Find the apparent power S.
A single-phase motor takes 40 kW at a power factor of 0.75 lagging from a 240 V supply. Find the line current I.
A single-phase motor takes 37 kW at a power factor of 0.75 lagging from a 240 V supply. Find the line current I.
A 12 V (rms), 1000 Hz source has an internal impedance Zs = 50 + j5 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A 12 V (rms), 1000 Hz source has an internal impedance Zs = 10 + j20 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
Answer key
- 1. Q = 262.3 var
- 2. S = 36.75 kVA
- 3. I = 222.2 A
- 4. I = 205.6 A
- 5. Pmax = 0.72 W
- 6. C = 7.958 µF