A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 15.5 A and 3030 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load draws 17 A (rms) from a 240 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
A load with impedance Z = 3 + j4 Ω is connected to a 240 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase motor takes 19 kW at a power factor of 0.8 lagging from a 240 V supply. Find the line current I.
A 10 V (rms), 50 Hz source has an internal impedance Zs = 50 + j20 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 21 kW at a power factor of 0.75 lagging from a 240 V, 50 Hz supply. A 470 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. cos φ = 0.8499
- 2. Q = 3101 var
- 3. Q = 9216 var
- 4. I = 98.96 A
- 5. Pmax = 0.5 W
- 6. cos φ = 0.9026