A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 8 A and 1728 W. Find the reactive power Q taken by the load.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 20 A and 2040 W. Find the power factor cos φ of the load.
An inductive load takes 7 A and 630 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A load with impedance Z = 12 + j9 Ω is connected to a 120 V (rms) single-phase supply. Find the real power P it absorbs.
A single-phase load takes 50 kW at a power factor of 0.7 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the capacitance C needed.
A single-phase load takes 25 kW at a power factor of 0.65 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the reactive power QC the capacitor must supply.
Answer key
- 1. Q = 836.9 var
- 2. cos φ = 0.85
- 3. R = 12.86 Ω
- 4. P = 768 W
- 5. C = 2081 µF
- 6. QC = 21.01 kvar