A single-phase load draws 16 A (rms) from a 240 V (rms) supply at a power factor of 0.9 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load draws 10 A (rms) from a 400 V (rms) supply at a power factor of 0.8 lagging. Find the real power P it takes.
A load with impedance Z = 9 + j12 Ω is connected to a 230 V (rms) single-phase supply. Find the reactive power Q it absorbs.
Two loads are connected in parallel to a 400 V single-phase supply: a 16 kW load at a power factor of 0.65 lagging and a 26 kW load at a power factor of 0.7 leading. Find the overall power factor cos φ seen by the supply.
A single-phase load takes 10 kW at a power factor of 0.6 lagging from a 230 V, 60 Hz supply. A 68 µF capacitor is connected in parallel with the load. Find the new line current I.
A single-phase load takes 50 kW at a power factor of 0.8 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the reactive power QC the capacitor must supply.
Answer key
- 1. Q = 1674 var
- 2. P = 3200 W
- 3. Q = 2821 var
- 4. cos φ = 0.9831
- 5. I = 67.84 A
- 6. QC = 13.28 kvar
Full step-by-step solutions: practise this topic on examproblems.com.