A single-phase load draws 18 A (rms) from a 240 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A load takes 42 kW of real power and 16.5 kvar of reactive power (lagging). Find the apparent power S.
A single-phase motor takes 30 kW at a power factor of 0.9 lagging from a 400 V supply. Find the line current I.
A single-phase motor takes 5 kW at a power factor of 0.85 lagging from a 400 V supply. Find the reactive power Q it draws.
A single-phase load takes 26 kW at a power factor of 0.65 lagging from a 230 V, 60 Hz supply. A 330 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A 10 V (rms), 60 Hz source has an internal impedance Zs = 4 + j30 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Answer key
- 1. Q = 3283 var
- 2. S = 45.12 kVA
- 3. I = 83.33 A
- 4. Q = 3.099 kvar
- 5. cos φ = 0.7374
- 6. Pmax = 6.25 W