A load takes 34.5 kW of real power and 14 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A single-phase load connected to a 400 V supply takes 23 kW and 13 kvar. Find the current I drawn from the supply.
A single-phase motor takes 36 kW at a power factor of 0.7 lagging from a 400 V supply. Find the reactive power Q it draws.
A single-phase motor takes 12 kW at a power factor of 0.7 lagging from a 230 V supply. Find the line current I.
A single-phase load takes 30 kW at a power factor of 0.7 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the new line current Inew.
A 200 kVA single-phase transformer supplies a load of 121 kW at a power factor of 0.85 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. S = 37.23 kVA
- 2. I = 66.05 A
- 3. Q = 36.73 kvar
- 4. I = 74.53 A
- 5. Inew = 78.95 A
- 6. ΔP = 64.41 kW