A single-phase load draws 3 A (rms) from a 240 V (rms) supply at a power factor of 0.65 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load draws 18 A (rms) from a 400 V (rms) supply at a power factor of 0.9 lagging. Find the real power P it takes.
A single-phase motor takes 36 kW at a power factor of 0.7 lagging from a 230 V supply. Find the line current I.
A single-phase motor takes 29 kW at a power factor of 0.7 lagging from a 400 V supply. Find the reactive power Q it draws.
A 120 V (rms), 1000 Hz source has an internal impedance Zs = 20 + j3 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 50 kW at a power factor of 0.75 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the reactive power QC the capacitor must supply.
Answer key
- 1. P = 468 W
- 2. P = 6480 W
- 3. I = 223.6 A
- 4. Q = 29.59 kvar
- 5. Pmax = 180 W
- 6. QC = 22.8 kvar