A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 7.5 A and 810 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load draws 12 A (rms) from a 120 V (rms) supply at a power factor of 0.9 lagging. Find the real power P it takes.
Two loads are connected in parallel to a 400 V single-phase supply: a 29 kW load at a power factor of 0.85 lagging and a 30 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
A load with impedance Z = 3 + j4 Ω is connected to a 230 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase load takes 19 kW at a power factor of 0.75 lagging from a 400 V, 50 Hz supply. A 68 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A single-phase load takes 10 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the reactive power QC the capacitor must supply.
Answer key
- 1. cos φ = 0.9
- 2. P = 1296 W
- 3. cos φ = 0.9566
- 4. Q = 8464 var
- 5. cos φ = 0.8185
- 6. QC = 6.848 kvar