A single-phase load draws 17 A (rms) from a 400 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 9.5 A and 1596 W. Find the power factor cos φ of the load.
A single-phase motor takes 24 kW at a power factor of 0.8 lagging from a 400 V supply. Find the reactive power Q it draws.
An inductive load takes 11 A and 1898 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase load takes 4 kW at a power factor of 0.6 lagging from a 230 V, 50 Hz supply. A 100 µF capacitor is connected in parallel with the load. Find the new line current I.
A single-phase load takes 5 kW at a power factor of 0.6 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
Answer key
- 1. Q = 5168 var
- 2. cos φ = 0.7
- 3. Q = 18 kvar
- 4. X = 13.83 Ω
- 5. I = 23.61 A
- 6. C = 283.4 µF
Full step-by-step solutions: practise this topic on examproblems.com.