A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 8 A and 720 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load draws 4 A (rms) from a 120 V (rms) supply at a power factor of 0.6 lagging. Find the reactive power Q it takes.
An inductive load takes 12.5 A and 2012 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A load with impedance Z = 8 + j6 Ω is connected to a 120 V (rms) single-phase supply. Find the real power P it absorbs.
A single-phase load takes 15 kW at a power factor of 0.75 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the reactive power QC the capacitor must supply.
A 200 kVA single-phase transformer supplies a load of 44 kW at a power factor of 0.6 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. cos φ = 0.75
- 2. Q = 384 var
- 3. X = 13.14 Ω
- 4. P = 1152 W
- 5. QC = 10.18 kvar
- 6. ΔP = 147.2 kW
Full step-by-step solutions: practise this topic on examproblems.com.