A single-phase load draws 19 A (rms) from a 230 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A load takes 33 kW of real power and 27 kvar of reactive power (lagging). Find the power factor cos φ.
Two loads are connected in parallel to a 240 V single-phase supply: a 9 kW load at a power factor of 0.85 lagging and a 12 kW load at a power factor of 0.7 lagging. Find the total current I drawn from the supply.
An inductive load takes 11.5 A and 828 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase load takes 30 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the capacitance C needed.
A 25 kVA single-phase transformer supplies a load of 13 kW at a power factor of 0.65 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. Q = 3321 var
- 2. cos φ = 0.774
- 3. I = 114.8 A
- 4. X = 8.348 Ω
- 5. C = 408.7 µF
- 6. ΔP = 6.849 kW
Full step-by-step solutions: practise this topic on examproblems.com.