A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 2 A and 299 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load connected to a 120 V supply takes 17.5 kW and 10 kvar. Find the current I drawn from the supply.
An inductive load takes 19 A and 2052 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A load with impedance Z = 12 + j5 Ω is connected to a 230 V (rms) single-phase supply. Find the real power P it absorbs.
A single-phase load takes 15 kW at a power factor of 0.65 lagging from a 400 V, 60 Hz supply. A 150 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A 50 kVA single-phase transformer supplies a load of 26 kW at a power factor of 0.7 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. cos φ = 0.65
- 2. I = 168 A
- 3. R = 5.684 Ω
- 4. P = 3756 W
- 5. cos φ = 0.8703
- 6. ΔP = 16.38 kW