A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 10.5 A and 819 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load draws 8 A (rms) from a 400 V (rms) supply at a power factor of 0.8 lagging. Find the reactive power Q it takes.
A single-phase motor takes 1 kW at a power factor of 0.75 lagging from a 400 V supply. Find the reactive power Q it draws.
A single-phase motor takes 17 kW at a power factor of 0.6 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase load takes 8 kW at a power factor of 0.65 lagging from a 240 V, 50 Hz supply. A 100 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A single-phase load takes 50 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the capacitance C needed.
Answer key
- 1. cos φ = 0.65
- 2. Q = 1920 var
- 3. Q = 0.8819 kvar
- 4. Q = 22.67 kvar
- 5. cos φ = 0.7276
- 6. C = 681.2 µF