A single-phase load connected to a 400 V supply takes 19 kW and 18.5 kvar. Find the current I drawn from the supply.
AC power & power factor worksheet with answers
A single-phase load draws 9 A (rms) from a 230 V (rms) supply at a power factor of 0.85 lagging. Find the reactive power Q it takes.
A single-phase motor takes 12 kW at a power factor of 0.7 lagging from a 240 V supply. Find the line current I.
An inductive load takes 16 A and 2208 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase load takes 10 kW at a power factor of 0.8 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
A single-phase load takes 25 kW at a power factor of 0.7 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the capacitance C needed.
Answer key
- 1. I = 66.3 A
- 2. Q = 1090 var
- 3. I = 71.43 A
- 4. X = 11.5 Ω
- 5. C = 274.3 µF
- 6. C = 684.1 µF