A single-phase load draws 19 A (rms) from a 230 V (rms) supply at a power factor of 0.7 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load draws 15 A (rms) from a 240 V (rms) supply at a power factor of 0.75 lagging. Find the reactive power Q it takes.
A single-phase motor takes 8 kW at a power factor of 0.6 lagging from a 230 V supply. Find the line current I.
An inductive load takes 4 A and 782 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A 50 kVA single-phase transformer supplies a load of 14 kW at a power factor of 0.65 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A 200 kVA single-phase transformer supplies a load of 48 kW at a power factor of 0.75 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. Q = 3121 var
- 2. Q = 2381 var
- 3. I = 57.97 A
- 4. X = 30.29 Ω
- 5. ΔP = 33.25 kW
- 6. ΔP = 147.5 kW
Full step-by-step solutions: practise this topic on examproblems.com.