A single-phase load draws 13 A (rms) from a 120 V (rms) supply at a power factor of 0.75 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load draws 3 A (rms) from a 240 V (rms) supply at a power factor of 0.75 lagging. Find the real power P it takes.
A single-phase motor takes 28 kW at a power factor of 0.75 lagging from a 240 V supply. Find the line current I.
Two loads are connected in parallel to a 240 V single-phase supply: a 4 kW load at a power factor of 0.6 lagging and a 25 kW load at a power factor of 0.9 lagging. Find the overall power factor cos φ seen by the supply.
A single-phase load takes 50 kW at a power factor of 0.7 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
A single-phase load takes 5 kW at a power factor of 0.65 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
Answer key
- 1. Q = 1032 var
- 2. P = 540 W
- 3. I = 155.6 A
- 4. cos φ = 0.857
- 5. C = 2458 µF
- 6. C = 266.9 µF