A load takes 38 kW of real power and 31.5 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A single-phase load draws 4 A (rms) from a 240 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
A single-phase motor takes 5 kW at a power factor of 0.6 lagging from a 400 V supply. Find the reactive power Q it draws.
Two loads are connected in parallel to a 400 V single-phase supply: a 15 kW load at a power factor of 0.85 lagging and a 25 kW load at a power factor of 0.8 leading. Find the overall power factor cos φ seen by the supply.
A single-phase load takes 20 kW at a power factor of 0.7 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the capacitance C needed.
A single-phase load takes 29 kW at a power factor of 0.8 lagging from a 230 V, 50 Hz supply. A 150 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. S = 49.36 kVA
- 2. P = 816 W
- 3. Q = 6.667 kvar
- 4. cos φ = 0.9732
- 5. C = 213.2 µF
- 6. cos φ = 0.8331