A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 15 A and 2340 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 6 A and 1080 W. Find the power factor cos φ of the load.
An inductive load takes 14.5 A and 2958 W from a 240 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
An inductive load takes 6 A and 1173 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A 100 V (rms), 60 Hz source has an internal impedance Zs = 20 + j6 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 9 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A 47 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. cos φ = 0.65
- 2. cos φ = 0.75
- 3. X = 8.719 Ω
- 4. X = 20.19 Ω
- 5. Pmax = 125 W
- 6. I = 47.29 A