A single-phase load connected to a 120 V supply takes 22.5 kW and 6 kvar. Find the current I drawn from the supply.
AC power & power factor worksheet with answers
A single-phase load connected to a 240 V supply takes 10.5 kW and 8 kvar. Find the current I drawn from the supply.
A load with impedance Z = 5 + j12 Ω is connected to a 120 V (rms) single-phase supply. Find the real power P it absorbs.
A single-phase motor takes 10 kW at a power factor of 0.75 lagging from a 240 V supply. Find the reactive power Q it draws.
A single-phase load takes 45 kW at a power factor of 0.65 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the capacitance C needed.
A single-phase load takes 45 kW at a power factor of 0.7 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the new line current Inew.
Answer key
- 1. I = 194.1 A
- 2. I = 55 A
- 3. P = 426 W
- 4. Q = 8.819 kvar
- 5. C = 2276 µF
- 6. Inew = 191.3 A