A load takes 50 kW of real power and 32 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A single-phase load draws 9 A (rms) from a 400 V (rms) supply at a power factor of 0.7 lagging. Find the real power P it takes.
A single-phase motor takes 23 kW at a power factor of 0.65 lagging from a 400 V supply. Find the reactive power Q it draws.
A single-phase motor takes 4 kW at a power factor of 0.6 lagging from a 240 V supply. Find the reactive power Q it draws.
A 15 kVA single-phase transformer supplies a load of 6 kW at a power factor of 0.6 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 40 kW at a power factor of 0.6 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the reactive power QC the capacitor must supply.
Answer key
- 1. S = 59.36 kVA
- 2. P = 2520 W
- 3. Q = 26.89 kvar
- 4. Q = 5.333 kvar
- 5. ΔP = 6.689 kW
- 6. QC = 45.21 kvar