A single-phase load draws 14 A (rms) from a 240 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load connected to a 230 V supply takes 6.5 kW and 7.5 kvar. Find the current I drawn from the supply.
A single-phase motor takes 35 kW at a power factor of 0.7 lagging from a 400 V supply. Find the reactive power Q it draws.
A load with impedance Z = 12 + j5 Ω is connected to a 120 V (rms) single-phase supply. Find the real power P it absorbs.
A 200 kVA single-phase transformer supplies a load of 55 kW at a power factor of 0.85 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A 200 kVA single-phase transformer supplies a load of 81 kW at a power factor of 0.6 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. P = 2856 W
- 2. I = 43.15 A
- 3. Q = 35.71 kvar
- 4. P = 1022 W
- 5. ΔP = 142.1 kW
- 6. ΔP = 87.33 kW
Full step-by-step solutions: practise this topic on examproblems.com.