A single-phase load draws 13 A (rms) from a 400 V (rms) supply at a power factor of 0.8 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 19.5 A and 1872 W. Find the power factor cos φ of the load.
Two loads are connected in parallel to a 400 V single-phase supply: a 26 kW load at a power factor of 0.75 lagging and a 6 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
An inductive load takes 2.5 A and 431 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A 150 kVA single-phase transformer supplies a load of 38 kW at a power factor of 0.65 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 40 kW at a power factor of 0.75 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
Answer key
- 1. P = 4160 W
- 2. cos φ = 0.8
- 3. cos φ = 0.8129
- 4. R = 68.96 Ω
- 5. ΔP = 105.3 kW
- 6. Inew = 111.1 A