A load takes 18 kW of real power and 14.5 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 19.5 A and 3978 W. Find the power factor cos φ of the load.
A single-phase motor takes 36 kW at a power factor of 0.8 lagging from a 400 V supply. Find the line current I.
A load with impedance Z = 3 + j4 Ω is connected to a 120 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase load takes 10 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the new line current Inew.
A single-phase load takes 28 kW at a power factor of 0.75 lagging from a 230 V, 50 Hz supply. A 470 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. cos φ = 0.7788
- 2. cos φ = 0.85
- 3. I = 112.5 A
- 4. Q = 2304 var
- 5. Inew = 42.52 A
- 6. I = 142.2 A
Full step-by-step solutions: practise this topic on examproblems.com.