A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 18.5 A and 3330 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load draws 20 A (rms) from a 240 V (rms) supply at a power factor of 0.75 lagging. Find the real power P it takes.
A single-phase motor takes 11 kW at a power factor of 0.6 lagging from a 240 V supply. Find the reactive power Q it draws.
An inductive load takes 2.5 A and 345 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A 200 kVA single-phase transformer supplies a load of 97 kW at a power factor of 0.75 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 9 kW at a power factor of 0.75 lagging from a 230 V, 50 Hz supply. A 150 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. cos φ = 0.75
- 2. P = 3600 W
- 3. Q = 14.67 kvar
- 4. R = 55.2 Ω
- 5. ΔP = 83.78 kW
- 6. cos φ = 0.8556