A single-phase load draws 5 A (rms) from a 400 V (rms) supply at a power factor of 0.6 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load draws 14 A (rms) from a 400 V (rms) supply at a power factor of 0.6 lagging. Find the real power P it takes.
A load with impedance Z = 24 + j7 Ω is connected to a 240 V (rms) single-phase supply. Find the real power P it absorbs.
An inductive load takes 6.5 A and 624 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase load takes 10 kW at a power factor of 0.8 lagging from a 400 V, 50 Hz supply. A 22 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A 75 kVA single-phase transformer supplies a load of 29 kW at a power factor of 0.8 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. Q = 1600 var
- 2. P = 3360 W
- 3. P = 2212 W
- 4. X = 11.08 Ω
- 5. cos φ = 0.8425
- 6. ΔP = 42.78 kW