A single-phase load draws 12 A (rms) from a 400 V (rms) supply at a power factor of 0.6 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 6.5 A and 1092 W. Find the power factor cos φ of the load.
A single-phase motor takes 10 kW at a power factor of 0.7 lagging from a 240 V supply. Find the reactive power Q it draws.
A single-phase motor takes 25 kW at a power factor of 0.85 lagging from a 230 V supply. Find the line current I.
A 150 kVA single-phase transformer supplies a load of 36 kW at a power factor of 0.8 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 35 kW at a power factor of 0.6 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the new line current Inew.
Answer key
- 1. Q = 3840 var
- 2. cos φ = 0.7
- 3. Q = 10.2 kvar
- 4. I = 127.9 A
- 5. ΔP = 111.5 kW
- 6. Inew = 148.8 A