A single-phase load draws 20 A (rms) from a 240 V (rms) supply at a power factor of 0.8 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load draws 4 A (rms) from a 120 V (rms) supply at a power factor of 0.7 lagging. Find the reactive power Q it takes.
A single-phase motor takes 36 kW at a power factor of 0.8 lagging from a 230 V supply. Find the reactive power Q it draws.
An inductive load takes 7.5 A and 1380 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase load takes 25 kW at a power factor of 0.6 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
A single-phase load takes 40 kW at a power factor of 0.8 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the new line current Inew.
Answer key
- 1. Q = 2880 var
- 2. Q = 342.8 var
- 3. Q = 27 kvar
- 4. X = 18.4 Ω
- 5. Inew = 69.44 A
- 6. Inew = 105.3 A
Full step-by-step solutions: practise this topic on examproblems.com.