A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 16.5 A and 3226 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load draws 14 A (rms) from a 400 V (rms) supply at a power factor of 0.6 lagging. Find the real power P it takes.
Two loads are connected in parallel to a 400 V single-phase supply: a 25 kW load at a power factor of 0.75 lagging and a 23 kW load at a power factor of 0.85 leading. Find the overall power factor cos φ seen by the supply.
A single-phase motor takes 27 kW at a power factor of 0.65 lagging from a 400 V supply. Find the line current I.
A single-phase load takes 10 kW at a power factor of 0.6 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the new line current Inew.
A single-phase load takes 21 kW at a power factor of 0.65 lagging from a 400 V, 60 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. cos φ = 0.8501
- 2. P = 3360 W
- 3. cos φ = 0.9871
- 4. I = 103.8 A
- 5. Inew = 43.86 A
- 6. cos φ = 0.8809