A load takes 35 kW of real power and 28.5 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A single-phase load draws 11 A (rms) from a 120 V (rms) supply at a power factor of 0.65 lagging. Find the real power P it takes.
A load with impedance Z = 3 + j4 Ω is connected to a 240 V (rms) single-phase supply. Find the real power P it absorbs.
Two loads are connected in parallel to a 230 V single-phase supply: a 6 kW load at a power factor of 0.85 lagging and an 18 kW heater (unity power factor). Find the total current I drawn from the supply.
A single-phase load takes 35 kW at a power factor of 0.6 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the reactive power QC the capacitor must supply.
A 200 kVA single-phase transformer supplies a load of 86 kW at a power factor of 0.65 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. cos φ = 0.7754
- 2. P = 858 W
- 3. P = 6912 W
- 4. I = 105.6 A
- 5. QC = 39.56 kvar
- 6. ΔP = 86.89 kW