A single-phase load draws 3 A (rms) from a 240 V (rms) supply at a power factor of 0.6 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load draws 3 A (rms) from a 240 V (rms) supply at a power factor of 0.8 lagging. Find the real power P it takes.
A single-phase motor takes 17 kW at a power factor of 0.9 lagging from a 240 V supply. Find the line current I.
A single-phase motor takes 4 kW at a power factor of 0.65 lagging from a 400 V supply. Find the line current I.
A single-phase load takes 20 kW at a power factor of 0.75 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
A 24 V (rms), 50 Hz source has an internal impedance Zs = 8 + j30 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Answer key
- 1. Q = 576 var
- 2. P = 576 W
- 3. I = 78.7 A
- 4. I = 15.38 A
- 5. C = 270.1 µF
- 6. Pmax = 18 W
Full step-by-step solutions: practise this topic on examproblems.com.