A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 3 A and 612 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load draws 17 A (rms) from a 240 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
A single-phase motor takes 30 kW at a power factor of 0.85 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase motor takes 7 kW at a power factor of 0.7 lagging from a 400 V supply. Find the reactive power Q it draws.
A single-phase load takes 21 kW at a power factor of 0.75 lagging from a 230 V, 60 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A single-phase load takes 5 kW at a power factor of 0.8 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the reactive power QC the capacitor must supply.
Answer key
- 1. cos φ = 0.85
- 2. Q = 3101 var
- 3. Q = 18.59 kvar
- 4. Q = 7.141 kvar
- 5. cos φ = 0.8296
- 6. QC = 1.62 kvar