A load takes 35.5 kW of real power and 13 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A single-phase load draws 13 A (rms) from a 230 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
A single-phase motor takes 21 kW at a power factor of 0.6 lagging from a 230 V supply. Find the reactive power Q it draws.
Two loads are connected in parallel to a 400 V single-phase supply: a 4 kW load at a power factor of 0.65 lagging and a 28 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
A 200 kVA single-phase transformer supplies a load of 52 kW at a power factor of 0.7 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A 200 kVA single-phase transformer supplies a load of 84 kW at a power factor of 0.8 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. S = 37.81 kVA
- 2. P = 2542 W
- 3. Q = 28 kvar
- 4. cos φ = 0.9895
- 5. ΔP = 140.8 kW
- 6. ΔP = 105.8 kW
Full step-by-step solutions: practise this topic on examproblems.com.